Programming
5-22
Advanced Setup Group (continued)
[
S
t
o
p
S
e
l
e
c
t]
Parameter # 10 Factory Default ‘‘Ramp”
[
S
t
o
p
S
e
l
e
c
t]
Parameter Type Read & Write
This parameter selects the stopping mode when the drive
re ei e a a i mma .
Units Text Settings ‘‘Coast”
Causes the Drive to Turn Off Immediately
Th
i
s p
arame
t
er
s
e
l
e
cts th
e
stopp
i
ng
m
od
e
w
h
e
n th
e
d
ri
v
e
receives a valid stop command.
‘‘Ramp” Drive Decelerates to 0 Hz, Then Turns Off – Requires
a Value In [Decel Time 1] or [Decel Time 2]
‘‘DC Brake”
Injects DC Braking Voltage Into the Motor – Requires a
Value in Both [Decel Hold Time] & [Decel Hold
Level].
‘‘S-Curve”
Drive ramps to stop using a fixed ‘‘S-Curve” profile.
Stop time is twice the selected decel time.
[
DC Hold
T
im
e]
Parameter # 12 Factory Default 0.0 Sec
[
DC Hold
T
im
e]
Parameter Type Read & Write Minimum 0.0 Sec
This value sets the amount of time that the [DC Hold
Level] voltage will be applied to the motor when the stop
mode is set to either ‘‘DC Brake” or ‘‘Ramp.” When in
‘‘Coast ” mode and the drive is stopped and restarted
within the [DC Hold Time] setting, the speed will resume
at the output frequency prior to the stop command.
Units 0.1 Seconds Maximum 150 Sec
[DC Hold Time]
Figure 5.13 Ramp Figure 5.14 DC Brake
Volts and Speed
y
Voltage
y
Stop Command
Stop Command
[DC Hold Time]
[DC Hold Level]
[DC Hold Level]
Time
Time
Speed
Speed
Voltage
Volts and Speed