Installation and Wiring 2-13
P46 Setting 3 - Momentary Run Forward/Run Reverse Control
This input mode allows the drive to respond to either a momentary or maintained
Run Forward or Run Reverse input, but requires a stop input to TB3 terminals 7
and 8 to command the drive to stop. In addition, this is the only input mode that
uses “level triggered” control logic, therefore once the stop command is removed
or if power is lost and restored, the drive will immediately restart if a maintained
Run command is present.
Momentary Run Fwd/Run Rev control Figure 2.7
➊
A momentary or maintained input can be used. If using maintained inputs, please read the
Attention
statement above.
➋
A normally closed maintained input is recommended. See
Attention
statement above.
ATTENTION: Hazard of injury exists due to unintended operation.
When
P46 - [Input Mode]
is set to 3, and the Run input is maintained,
the Run inputs do not need to be toggled after a Stop input for the
drive to run again. A Stop function is provided only when the Stop
input is active (open).
Stop
➋
567
8
Common
Run Forward
➊
Run Reverse
➊
TB3
Note: A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.