Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 3
1756 ControlLogix Chassis Specifications
Table 3 - Environmental Specifications - ControlLogix Standard Chassis
Attribute 1756-A4/B, 1756-A7/B, 1756-A10/B, 1756-A13/B,
1756-A17/B
1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C,
1756-A17/C
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F) -25…60 °C (-13…140 °F)
Temperature, surrounding air 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g 30 g
Emissions IEC 61000-6-4
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Table 4 - Certifications - ControlLogix Standard Chassis
Certification
(1)
1756-A4/B 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B 1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C,
1756-A17/C
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.
CSA Certified Process Control Equipment. See CSA File
LR054689.
CSA Certified Process Control Equipment for Class I,
Division 2 Group A,B,C,D Hazardous Locations. See CSA
FileLR069960.
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations.
CE European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM Australian Radiocommunications Act, compliant with:
EN 61000-6-4; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres,
Protection “n”
• EN 60079-0; General Requirements
• II 3 G Ex nA IIC T4 Gc X
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres,
Protection “n”
• EN 60079-0; General Requirements
• II 3 G Ex nA IIC T5 Gc X
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres,
Protection “n”
• EN 60079-0; General Requirements
• II 3 G Ex nA IIC T4 Gc
• DEMKO13ATEX1325026X
Kommentare zu diesen Handbüchern