Publication DNET-UM004A-EN-P - March 2004
15-2 Using POINT™ I/O Modules on a DeviceNet Network
Choose a Connecting
Device
To choose the device that connects your POINT I/O modules to the
DeviceNet network, consider the following:
total number of devices on the network
type of devices on the network
topology and length of the network
current requirements of the POINT I/O modules
P
O
I
N
T
I/
O
P
O
I
N
T
I/
O
P
O
I
N
T
I/
O
P
D
N
P
O
I
N
T
I/
O
P
O
I
N
T
I/
O
A
D
N
subnet
123
4
P
O
I
N
T
I/
O
P
O
I
N
T
I/
O
A
D
N
X
subnet
5
subnet
device device
P
O
I
N
T
I/
O
P
O
I
N
T
I/
O
Block I/O
78
6
POINT I/O Interface
1734-PDN
POINT I/O Adapter
1734-ADN
POINT I/O Adapter
1734-ADNX
POINTBlock I/O Module
1734D
main DeviceNet network
Each I/O module uses
an address on the
main DeviceNet
network.
Total current
requirements of the
I/O modules must be
1.3A or less.
Consolidates the I/O
module into a single
address on the main
DeviceNet network.
Total current requirements
of I/O modules can be
greater than 1.3A.
The subnet lets you:
connect other types of
DeviceNet devices to the
subnet
Place devices beyond the
limits of the main
DeviceNet network
If you are also using a
POINTBlock I/O
module, connect your
other POINT I/O
modules to that
module.